Sprinkler inspection software that turns an ITM visit into a tagged, dated record the fire marshal accepts
Sprinkler inspection ITM is the inspection, testing and maintenance cycle that keeps a water based fire protection system in service, run on frequencies that range from weekly gauge checks to five year internal pipe examinations. OSHA requires a main drain flow test on each system annually and the inspector's test valve opened at least every two years, and Florida requires the resulting NFPA 25 report to reach the building owner within 30 days and to be kept by the contractor for at least 10 years. Neurobird holds the system, the frequency, the deficiency and the tag on one record.
Neurobird Sprinkler Inspection ITM in short
- Hold every frequency each system owes, from weekly gauges to five year internal examinations
- Record a deficiency with its severity, so a critical finding starts its own clock
- Track the tag on the main water control valve as a record, not as a photograph
- 1910.159 The OSHA standard requiring a main drain flow test on each sprinkler system annually and the inspector's test valve opened at least every two years to confirm the system operates. OSHA 29 CFR 1910.159
- 30 minutes Minimum duration of design water flow that every automatic water supply must be capable of providing, with an auxiliary supply required when the automatic one is out of service. 29 CFR 1910.159
- Pricing runs 179 to 1400 US dollars per month across 3 tiers. Early access is free.
What fire protection contractors actually deal with
Why it stays broken
An ITM programme is a stack of different frequencies on the same system, and the frequency belongs to a standard while the deadline belongs to a state rule. OSHA sets an annual main drain flow test and a two year inspector's test valve check, Florida sets 30 day owner notice, 90 day noncritical correction and 72 hour impairment reporting, and the tag on the valve is the only thing an inspector sees. Field service software tracks visits, not frequencies, so the calendar lives in somebody's head.
Under 29 CFR 1910.159 the employer must have a main drain flow test performed on each sprinkler system annually and the inspector's test valve opened at least every two years.
Fire Protection contractors complete a documented inspection, testing, and maintenance of each system and are required to submit their findings to Portland Fire & Rescue within 30 days of the visit to your business.
The frequency board, as your scheduler would run it
Close an item to see the next due date and the tag on the riser change together.
| Requirement | Status | Next due | |
|---|---|---|---|
| Dry system 2, quarterly inspection, low air alarm noted | current | in 42d | |
| Standpipe, 5 year internal pipe examination, scheduled | due soon | in 9d | |
| Riser 1, wet system, annual main drain flow test due | current | in 120d | |
| Fire pump, weekly churn test, 3 weeks outstanding | overdue | 3d late | |
| Fire pump, weekly churn test, 3 weeks outstanding | current | in 64d |
Tick a requirement to file evidence against it.
Neurobird Sprinkler Inspection ITM Compliance Platform
One record per system: the frequencies it owes, the last time each was performed, every deficiency found with its severity, the tag colour hanging on the valve and the report that went to the owner.
- 1Hold every frequency each system owes, from weekly gauges to five year internal examinations
- 2Record a deficiency with its severity, so a critical finding starts its own clock
- 3Track the tag on the main water control valve as a record, not as a photograph
- 4Prove the NFPA 25 report reached the owner, and when the correction window closes
What changes with Neurobird Sprinkler Inspection ITM?
The same work, read left to right: how it runs today, and how it runs once the record is in one place.
| Today | With Neurobird Sprinkler Inspection ITM |
|---|---|
| A red tag goes on a riser and the only record of it is a photograph on a technician's phone | Hold every frequency each system owes, from weekly gauges to five year internal examinations |
| Quarterly, semiannual and five year items on one building fall out of step until a survey finds them | Record a deficiency with its severity, so a critical finding starts its own clock |
| The owner says the report never arrived and there is no proof of the date it was sent | Track the tag on the main water control valve as a record, not as a photograph |
Who is this for?
The same riser, three different shops.
You inspect and repair the same buildings
Inspection finds it, service fixes it, and both are you. You need the deficiency to become a work order without being retyped.
You run scheduled ITM at scale
Hundreds of buildings, each with its own frequency stack. You need the calendar to be a property of the system, not of a scheduler.
You hold the buildings, not the trucks
Reports arrive from several contractors in several formats, some still built around 1910.159 alone. You need one place that shows which systems are current and which are tagged.
How does Neurobird Sprinkler Inspection ITM work?
Register the system
Each riser, pump, backflow assembly and standpipe on the property carries its own frequency list, so a semiannual item cannot ride along on an annual visit.
Inspect and tag
The technician records the result, the deficiency and its severity, and the tag that goes on the valve is generated from that record rather than written out by hand.
Notify and close
The report goes to the owner with a date, the correction window runs against that date, and an impairment or an uncorrected critical deficiency escalates before the deadline passes.
What the rules say about testing a sprinkler system
Federal maintenance duties, a state ITM rule with hard notice deadlines, and the federal health care standard that adopts NFPA 25 by reference.
The OSHA standard requiring a main drain flow test on each sprinkler system annually and the inspector's test valve opened at least every two years to confirm the system operates.
OSHA 29 CFR 1910.159Minimum duration of design water flow that every automatic water supply must be capable of providing, with an auxiliary supply required when the automatic one is out of service.
29 CFR 1910.159Minimum vertical clearance, given as 45.7 cm in the rule, required between sprinklers and the material stored below them, and any system with more than 20 sprinklers needs a local waterflow alarm.
29 CFR 1910.159Florida deadline for the inspecting contractor to get a copy of the NFPA 25 inspection report to the building owner, with a further 90 days for noncritical deficiencies to be corrected before the local authority is notified.
Florida Administrative Code 69A-46.041Time an impairment may go uncorrected in Florida before the inspecting contractor must notify the local authority having jurisdiction, with critical deficiencies reported to the owner within 24 hours.
Florida Administrative Code 69A-46.041How long a Florida contractor must keep inspection records for a fire protection system, produced to the State Fire Marshal on request in whatever format the contractor uses.
Florida Administrative Code 69A-46.041Sprinkler inspection itm software questions, answered
Key terms
- What is sprinkler inspection ITM?
- ITM stands for inspection, testing and maintenance: the recurring work that keeps a water based fire protection system in service. Frequencies run from weekly gauge readings to five year internal pipe examinations, and 29 CFR 1910.159 separately requires an annual main drain flow test and the inspector's test valve opened at least every two years.
- What are the deadlines after a deficiency is found?
- They are set by the authority having jurisdiction. Florida is a clear example: the owner gets a copy of the NFPA 25 report within 30 days, noncritical deficiencies have 90 days before the local authority is told, critical deficiencies are reported to the owner within 24 hours, and an uncorrected impairment is escalated within 72 hours.
Does this replace our field service software?
No. It sits beside it. Field service moves technicians and invoices. This holds the frequency stack per system, the deficiency with its severity, the tag on the valve and the proof the report reached the owner.
How does it handle buildings in several jurisdictions?
The frequency comes from the standard and the deadline comes from the jurisdiction, so both are properties of the building. A Florida site carries the Florida notice clock, another site carries its own, and the technician sees the same board either way.
Can an owner see which systems are current?
Yes. Each building has one view showing systems, frequencies, outstanding deficiencies and tag status. You choose what the owner sees and what stays inside the shop.
Why we are building this
W
e
w
e
n
t
l
o
o
k
i
n
g
f
o
r
w
o
r
k
w
h
e
r
e
t
h
e
p
a
p
e
r
t
r
a
i
l
i
s
t
h
e
p
r
o
d
u
c
t
,
a
n
d
s
p
r
i
n
k
l
e
r
I
T
M
k
e
p
t
c
o
m
i
n
g
u
p
.
T
h
e
f
r
e
q
u
e
n
c
i
e
s
c
o
m
e
f
r
o
m
a
s
t
a
n
d
a
r
d
,
t
h
e
d
e
a
d
l
i
n
e
s
c
o
m
e
f
r
o
m
a
s
t
a
t
e
r
u
l
e
,
a
n
d
t
h
e
w
h
o
l
e
t
h
i
n
g
h
a
n
g
s
o
n
a
c
o
l
o
u
r
e
d
t
a
g
t
i
e
d
t
o
a
v
a
l
v
e
.
T
h
a
t
i
s
a
r
e
c
o
r
d
p
r
o
b
l
e
m
,
a
n
d
r
e
c
o
r
d
p
r
o
b
l
e
m
s
a
r
e
w
h
a
t
w
e
b
u
i
l
d
.
T
h
e
r
e
g
u
l
a
t
i
o
n
s
w
e
r
e
a
d
w
h
i
l
e
s
c
o
p
i
n
g
t
h
i
s
a
r
e
l
i
n
k
e
d
a
b
o
v
e
,
s
o
y
o
u
c
a
n
c
h
e
c
k
o
u
r
r
e
a
d
i
n
g
o
f
t
h
e
m
r
a
t
h
e
r
t
h
a
n
t
a
k
e
o
u
r
w
o
r
d
f
o
r
i
t
.
I
f
w
e
h
a
v
e
a
f
r
e
q
u
e
n
c
y
w
r
o
n
g
,
t
e
l
l
u
s
a
n
d
w
e
w
i
l
l
f
i
x
i
t
.
Where the requirement comes from
Primary sources, straight from the regulators.
- OSHA 29 CFR 1910.159, automatic sprinkler systems Annual main drain flow test, the two year inspector's test valve check and the acceptance test list.
- 29 CFR 1910.159 at Cornell LII Water supply duration, alarm thresholds and the 45.7 cm clearance rule, with 1910.160 sitting alongside it for fixed systems.
- Florida Administrative Code 69A-46.041, ITM for fire protection systems Tag colours, notice deadlines, correction windows, the 10 year retention rule and Form DFS-K3-2015.
- 42 CFR 483.90, physical environment for long term care facilities Where CMS adopts the 1998 edition of NFPA 25 and the 1999 edition of NFPA 13 by reference, and what happens when a system is shut down for more than 10 hours.
- CMS Life Safety Code guidance How the 2012 edition of the Life Safety Code is surveyed in certified facilities, which is who reads your report.
- Portland Fire and Rescue, ITM programme A worked local example of how an authority having jurisdiction actually collects ITM reports.
How much does Neurobird Sprinkler Inspection ITM cost?
Priced per shop because the licence, the tags and the 10 year retention duty belong to the contractor, not to the building. Buildings, systems, frequencies and deficiencies are unlimited on every tier.
- Up to 3 inspectors
- Unlimited systems
- Frequency scheduling
- Tag and deficiency log
- Unlimited inspectors
- Jurisdiction notice clocks
- Report delivery proof
- Deficiency to work order
- Several branches
- Owner portal
- State fire marshal exports
- Priority support
Get free early access
Early access means we load your frequency stacks and your jurisdiction's notice deadlines before you type anything, and the account stays free while we do it.
Straight answer on where this is: The software is in development. Nothing is purchasable today. Early access means you shape it and pay nothing while we build.
Prefer email? Write to office@neurobird.com and a person will reply. No autoresponder.